Not Yet Classified

This recall has not yet been classified by risk level.

Gamewell-FCI Recalls Fire Alarm Panels Due to Failure to Alert of a Fire, Smoke or CO

Date: March 31, 2016
Company: Gamewell-FCI of Northford, Conn.
Status: Ongoing
Source: CPSC

What You Should Do

Stop using this product immediately. Do not consume, use, or distribute it.

Consumers should immediately contact the distributor to obtain the free repair, a firmware upgrade. Options: Repair

Affected Products

This recall is for the ILI-MB-E3 and ILI-S-E3 Gamewell-FCI fire alarm panels in commercial buildings. This issue is limited to a specific configuration of Signaling Line Circuit (SLC) devices. To occur, the SLC must include at least two of the following detectors in any combination: Acclimate, 4-Warn, Photo/CO and iFAAST. The issue would occur only if the detectors are addressed within the same FlashScan polling group. Detectors installed in a different combination are not affected.

Why Was This Recalled?

When configured in a certain way, the panels can become non-responsive and connected detectors in the area can fail to detect and respond to an alarm.

Where Was This Sold?

Distribution information not available.

About Gamewell-FCI of Northford, Conn.

Gamewell-FCI of Northford, Conn. has 1 total recall tracked by RecallDetector.